Transcript
00:00Here we are at the connector products test lab.
00:03What we've done is we use about 900 amps to raise the ambient temperature
00:10over 100 degrees over the uh control conductor.
00:15So you can see here, ambient temperature is
00:2273 °F depth measured by our thermal couples
00:28here taking the ambient temperature.
00:34Our control conductor is at 288 °F
00:43which is taken measurement by thermal couple here.
00:51And we have four connectors set up in the loop.
00:55You can see as we go through the thermocouple, this one's about 80 degrees cooler.
01:03Uh This one's about no more than 100 degrees cooler.
01:11You can see that all the connectors are running much cooler.
01:15Then the control cable, this is our standard test transformer.
01:22Um It's been in clothes type.
01:26We set up our loop with thermal stabilizers and connectors 2 ft in
01:32between. So from the connector to the stabilizer is 2 ft
01:39JW to connect her 2 ft, they was to connect their 2 ft
01:46as the standard specifies there's 4 ft around the control,
01:51the next stabilizer and then the next connector and the final connector.
01:59So this is our test on 795 double ac 37 strand at
02:05approximately 900.