text.skipToContent text.skipToNavigation

453/UNIV Mining Cable Gland

By Hawke 
By Hawke
The 453/Universal Cable Gland a Group I certified cable gland for use in mining applications. Dual Certified ATEX/IECEx (along with many more) for use in Increased Safety (Exe) and Flameproof (Exd) protection concepts. Designed for use with single wire armour, wire braid, steel tape armour, elastomer and plastic insulated cables. The gland provides a low smoke, zero halogen IP and retention seal onto the cable outer sheath. For particular use with cables that exhibit 'Cold Flow' characteristics.
  • Metallic body construction
  • Inspectable Deluge Seal - Offering IP66, IP67, IP68 & IP69
  • Passive Diaphragm Exd Seal onto cable inner sheath - particularly suitable for cables exhibiting cold flow characteristics
  • Reversible Armour Clamp - For all types of armour, braid and tape
  • Patented Cable Gland Tightening Guide - Helps prevent damage caused by over tightening
  • Unique Rear IP Seal - Offering ultimate sealing over an extremely wide cable acceptance range
  • Available with metric or NPT entry threadforms

See technical section of the datasheet for installation rules and regulations. Visit www.universalreloaded.com to download a full version of the catalogue.
Click here for Resource Search tool.

More Options

Where to Buy

Product Details

General

Application Group 1 Mining Applications
Ingress Protection
  • IP66, IP67, IP68 (30 metres for 7 days special instructions apply)
  • IP69 to IEC/EN 60529
  • NEMA 4X
Material Manufactured in Brass, Nickel Plated Brass or 316L Stainless Steel
Operating Temperature -60°C to +80 °C
Series Cable Glands for Group I Hazardous Areas

Certifications and Compliance

ATEX File Number CML 19ATEX1166X and CML 19.0044X
Certification
  • ATEX: CML 19ATEX1166X
  • EAC: No EA3C RU C-GB.HA91.B.00264/21
  • EQM: 20-11-27224/Q20-11-000979/NB0007
  • IECEx: CML 19.0044X
  • UKEx: CML 21UKEX1160X
Hazardous Rating(s) Ex IM2 Ex db I Mb, Ex eb I Mb
Industry Standard(s)
  • IEC/EN 62444 (Anchorage Type D)
  • IEC/EN 60079-0, 1, 7
Ratings IK10 to IEC 62262