text.skipToContent text.skipToNavigation

EVP Arrester (152 kV MCOV / Uc)

by OHIO BRASS 

Catalog ID: EVP0152003002

IEEE Station Class / IEC Station Medium Polymer Housed Surge Arrester

  • EVP solid core station arresters comply with the latest revision of IEEE C62.11 and IEC 60099-4
  • Long lasting ESPTM housing material with superior mechanical strength and electrical characteristics
  • Robust sealing system protects internal components from moisture ingress to extend service lifetime
  • High quality MOV discs made in Wadsworth, Ohio since 1978
  • Assembled in Aiken, South Carolina
  • 100% routine tested

Product Details

General

Cantilever Bending Strength - Max. 20,000 lb
Color Gray Housing
Material ESP™ Polymer Housing
Mounting Hardware Single Eyebolt Terminals
Mounting Position Upright
Type Station

Dimensions

Diameter - Bolt Circle Variable 8.75 to 10 in
Diameter - Lug Hole .56 in (14.224 mm)
Diameter - Ring 27.9 in / 14.5 in
Diameter - Single Bolt Hole(s) 0.50 in
Height 83.5 in
Maximum Operating Altitude 12000 ft
Minimum Mounting Spacing on Center (Sea Level) - Phase to Ground 65.8 in (1671 mm)
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase 79.7 in (2024 mm)
Thickness - Lug 1.25 in (31.75 mm)
Weight 120 lb

Electrical Ratings

Creep and Leakage Distance 215.8 in (5481 mm)
Duty Cycle 192 kV
Frequency Rating 48-62 Hz
MCOV 152 kV
Maximum .5 Microsecond Discharge Volts @ Classifying Current 510.0 kV
Maximum Discharge Voltage
  • 390.7 kV @ 1.5 kA
  • 410.5 kV @ 3 kA
  • 430.4 kV @ 5 kA
  • 461.8 kV @ 10 kA
  • 499.2 kV @ 20 kA
  • 569.4 kV @ 40 kA
Maximum Switching Surge Protective Level @ 1000A 381.4
Pressure Relief Capability-Symmetrical rms (kA) 63
Withstand Voltage - 60 Hz Wet 395 kV
Withstand Voltage - Lightning Impulse 1006 kV
Withstand Voltage - Switching Impulse 843 kV

Certifications and Compliance

Industry Standard(s) IEEE/IEC