MH4 Arrester (264 kV Rated, 7748 mm Creep Distance, AA Hardware)

Brand:

OHIO BRASS

Catalog ID:

MH4362GM264AA

IEC Station High / Porcelain Housed Surge Arrester

IEC Porcelain station class arresters for substation protection

  • IEC porcelain Station High class arrester
  • IEEE 693 High Performance Qualification
  • High quality MOV discs made in Wadsworth, Ohio since 1978
  • Arresters assembled in Aiken, South Carolina
  • 100% routine tested

Product details

General

Application
Substation
Color
Gray Housing
Material
Porcelain Housing
Mounting Position
Upright
Type
Station

Dimensions

Bolt Circle Diameter
254 mm
Diameter - Single Bolt Hole(s)
14 mm
Height
2759.2 mm
Minimum Mounting Spacing on Center (Sea Level) - Phase to
60.4 in (1534 mm)
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
68.9 in (1751 mm)

Electrical Ratings

Creep and Leakage Distance
305 in (7748 mm)
Duty Cycle
264 kV
Frequency Rating
48-62 Hz
Maximum Discharge Voltage
  • 546 kV @ 1.5 kA
  • 567 kV @ 3 kA
  • 587 kV @ 5 kA
  • 616 kV @ 10 kA
  • 660 kV @ 20 kA
  • 726 kV @ 40 kA
Maximum Switching Surge Protective Level @ 1000A
527 kV
Maximum Switching Surge Protective Level @ 2000A
546 kV
Maximum Switching Surge Protective Level @ 500A
512 kV
MCOV
211.2 kV
Minimum Strike
2198 mm
Pressure Relief Capability-Symmetrical rms (kA)
63
Voltage - Line
362 kV
Withstand Voltage - 60 Hz Wet
690 kV
Withstand Voltage - Lightning Impulse
1206 kV
Withstand Voltage - Switching Impulse
1064 kV

Conductor Related

Conductor Type
Cu/Al (AWG #4 - 500 MCM)

Certifications And Compliance

Industry Standard(s)
IEC