Image of YGL34C29 Conector de rejilla cruzada de compresiĆ³n YGL34C29
Image of YGL34C29 Conector de rejilla cruzada de compresiĆ³n YGL34C29

Conector de rejilla cruzada de compresiĆ³n YGL34C29

Marca:

Burndy

ID del CatƔlogo:

YGL34C29

Conector de malla cruzada de compresiĆ³n de cobre, 250 kcmil - 500 kcmil o varilla de tierra de 5/8" - 3/4" o barra de refuerzo # 5 - 6, 2 AWG (Str.) - 250 kcmil.

  • Irreversible compression ground grid cross connector allows adjustment of the compression elements prior to installation
  • UL467 Listed
  • Acceptable for Direct Burial in earth and concrete
  • Prefilled with PENETROXā„¢ compound and strip sealed

Features: An Irreversible Compression Ground Grid Cross Connector Which Allows Adjustment Of The Compression Elements Prior To Installation, Only Six Connectors And Four Dies Are Required To Install All Combinations From 6 AWG Solid Through 500 KCMIL, UL467 Listed Acceptable For Direct Burial In Earth And Concrete, Prefilled With PENETROX Compound And Strip Sealed, Dimensions In Brackets Represent Lightning Protection Conductors, Die Index: 997 Element A, 997 Element B, Conductor Type: Run: Commercial Stranded Copper, Rebar, Ground Rod, Tools, Die Set Catalog Number, And (number Of Crimps): Element A: Y750/Y35/Y39 HYPRESS Tool, PU998 Die, (1), PAT750-18V Tool, PU998 Polarized Die, (1), Y45 HYPRESS Tool, S998 Or PU998 Die, (1), Y46 HYPRESS Tool, PU998 OR PU998 Die, (1), Element B: Y750/Y35/Y39 HYPRESS Tool, U997 Die, (1), PAT750-18V Tool, U997P Polarized Die, (1), Y45 HYPRESS Tool, U997 Die, (1), Y46 HYPRESS Tool, U997 Die, (1), Rebar Size: #5 - #6, Ground Rod Size: 5/8 - 3/4 IN, Cable To Cable : Element A: 250 KCMIL (0.575) - 500 KCMIL (0.813), Element B: 2 AWG Stranded (.292) 250 KCMIL (0.575), Cable To Ground Rod: Element A: 5/8 - 3/4 IN Rod, Element B: 2 AWG Stranded (0.292) 250 KCMIL (0.575), Cable To Rebar: Element A: #5 - #6 Rebar

Detalles del producto

General

Application

For Direct Burial In Earth And Concrete

Catalog Number

YGL34C29

Connector Type

Tap

Die Index

997;998

EU RoHS Indicator

Yes

Material

Copper

Oxide Inhibitor Type

Penetrox E

Plated

N

Plating Type

Unplated

Prefilled Oxide Inhibitor

Y

Sub Brand

HYGROUND, HYGRID

Trade Name

HYGRIDā„¢

Type

Taps

UPC

781810220047

UPC 12 Digit

7818102200477

Dimensiones

Dimension - B Length fraction

3/4 in

Dimension - B Length inch

0.75 in

Dimension - D inch

0.50 in

Dimension - L Length Overall mm

64 mm

Dimension - Length Overall inch

2.50 in

Dimension - Pad Width inch

2.09 in

Relacionado con el Conductor

Conductor - Copper Str Size A

250 kcmil;300 kcmil;350 kcmil;400 kcmil;450 kcmil;500 kcmil

Conductor - Copper Str Size A Range

250 kcmil-500 kcmil

Conductor - Copper Str Size B

2 AWG;1 AWG;1/0 ;2/0 AWG;3/0 AWG;4/0 AWG;250 kcmil

Conductor - Copper Str Size B Range

2 AWG-250 kcmil

Conductor - Rebar Size A

5 ;6

Conductor - Rebar Size A Range

5 -6

Conductor - Rod Size A

5/8 in;3/4 in

Conductor - Rod Size A Range

5/8 in-3/4 in

Conductor Type

  • CU C Solid-Size A
  • CU C Str-Size A
  • Rod-Size A
  • Rebar-Size A
  • CU C Solid-Size B
  • CU C Str-Size B

Certificaciones y Cumplimiento

Certification - CSA Approved

Yes

Certification - cULus

No

Certification - ETL

No

Certification - UL Listed Direct Burial

Yes

Certification - UL Recognized

No

Industry Standard(s)

  • UL467
  • IEEE 837

Standards - Industry Standards Met

  • UL467
  • IEEE 837

Standards - RoHS Compliance Status

CM

UL Listed

Yes

LogĆ­stica

Carton Quantity

6

Pallet Quantity

1776

Recursos y descargas