text.skipToContent text.skipToNavigation

Protecta*Lite Arrester (160 kV MCOV)

by OHIO BRASS 

Catalog ID: 639160A2X6002

This web listing represents a sampling of typical configurations. Protecta*Lite Arrester assemblies can be customized for all distribution and transmission lines.

Selection of arrester MCOV size is based upon the maximum continuous voltage that is applied across the arrester in service (line-to-ground). For arresters on effectively grounded neutral systems, this is normally the maximum line-to-ground voltage

Example: 84 kV on a 138 kV system. For ungrounded or impedance-grounded systems, the MCOV should be at least 90 percent of maximum phase-to-phase voltage.

For more information about arrester selection, please contact your Hubbell Power Systems representative.

  • To learn more about how Protecta*Lite improves line performance, click here to visit our blog.
  • Product Details

    General

    Application Above 35 kV
    Type Line Arresters
    UPC 096359685395

    Electrical Ratings

    Creep and Leakage Distance 314.6 in (7990.8 mm)
    Duty Cycle 192 kV
    Frequency Rating 48-62 Hz
    MCOV 160 kV
    Maximum .5 Microsecond Discharge Volts @ Classifying Current 507.0 kV
    Maximum Discharge Voltage
    • 394 kV @ 1.5 kA
    • 413 kV @ 3 kA
    • 431 kV @ 5 kA
    • 460 kV @ 10 kA
    • 498 kV @ 20 kA
    • 554 kV @ 40 kA
    Maximum Switching Surge Protective Level @ 500A 357.0 kV
    Pressure Relief Capability-Symmetrical rms (kA) 63
    Voltage - Line 230 kV

    Certifications and Compliance

    Industry Standard(s) IEEE/IEC