WBP_ATD2000C_PRODIMAGE
WBP_ATD2000C_PRODIMAGE
WBP_ATD2000C_alt-2_PRODIMAGE
WBP_ATD2000C_App-1_PRODIMAGE
+2
WBP_ATD2000C_alt-1_PRODIMAGE

Switches and Lighting Controls, Occupancy Sensors, Adaptive Technology Dual (Ultrasonic and PIR) Ceiling Sensors, 2000 Square Feet CoverageWithRelay

Brand:

Hubbell Wiring Device-Kellems

Catalog ID:

ATD2000CRP

Switches and Lighting Controls, Occupancy Sensors, Adaptive Technology Dual (Ultrasonic and PIR) Ceiling Sensors, 2000 Square Feet CoverageWithRelay

Adaptive Dual Technology combines Ultrasonic and Passive Infrared technology, minimizing the risk of lights turning ON when the space is unoccupied. Once occupancy is detected by both technologies within the space lights are turned ON, only one technology is necessary to keep the lights ON. Adaptive technology provides better control. Hubbell’s patented breakthrough in advanced control feature smart microprocessors constantly monitoring the controlled area and adjust the sensitivity and timer based on environmental history. The optimum choice when performance is paramount.

  • Relay to interface with auxiliary systems such as HVAC
  • Red LED indicates passive infrared detection and Green LED indicates ultrasonic detection
  • "Install and Forget" operation. Auto-adjusting adaptive technology eliminates manual adjustments

With Photocell and Relay

Product details

General

Application
Color
  • White
Environmental Conditions
Indoor Dry Unless Protected By Additional Means
EU RoHS Indicator
Yes
Humidity
0% to 95% non-condensing relative humidity
Indicator(s) Type
PIR= Red LED, Ultrasonic= Green LED
Item Type
Low voltage Ceiling Sensors
Load Capacity
Load Is A Function Of The Control Unit
Material
ABS (Acrylonitrile butance styrene - Thermoplastic polymer)
Material - Mounting Hardware
Screw Mounting
Mounting Type
Ceiling Mount
OEM Brand Name
Hubbell Wiring Device-Kellems
Operating Cycles
6,000 Cycles Minimum
Operating Temperature
32 Deg F to 104 Deg F (0 Deg C to 40 Deg C)
Performance
  • Controls - Ambient Light - 1 to 1000 foot candles
  • Controls - Sensitivity - Adaptive 0 to 100%
  • Controls - Time Delay - Test (8 seconds), adaptive 8 to 40 minutes
  • Electrical - Isolated Relay - Normally open and normally closed terminals available
  • Electrical - Power Requirements - 24V DC nominal, 33mA from Hubbell CU series control unit
  • Environmental - Operating Temperature - 32°F to 104°F (0°C to 40°C) with rate of change not exceeding 20°F (11°C) per hour
  • Environmental - Storage Temperature - -20°F to 150°F (-29°C to 65°C), 0% to 95% non-condensing relative humidity
  • Sensing Indicators - Passive Infrared - Red LED
  • Sensing Indicators - Ultrasonic - Green LED
Photocell
Yes
Series
Dual
Storage Temperature Range
-20°F to 150°F (-29°C to 65°C)
Style
Ceiling Mount
Type
  • Sensors
  • Sensors
UPC
783585392400

Dimensions

Diameter
4.5 in
Height
1.5 in
Mounting Height
8-12 ft

Electrical Ratings

Sensitivity
Adaptive 0 to 100%
Supply Voltage
24V DC From Control Unit
Voltage Rating
24 VDC
Voltage Rating Description
24V DC

Certifications And Compliance

Industry Standard(s)
  • ASHRAE 90.1 Compliant
  • cULus Listed To UL244A

Logistics

Carton Quantity
10
Pallet Quantity
840