text.skipToContent text.skipToNavigation

Switches and Lighting Controls, Occupancy Sensors, Adaptive Technology Passive Infrared Ceiling Sensor, 1500 Square Feet Coverage, With Relay

By Hubbell Wiring Device-Kellems 

Catalog ID: ATP1500CRP

By Hubbell Wiring Device-Kellems
Catalog ID:  ATP1500CRP
Switches and Lighting Controls, Occupancy Sensors, Adaptive Technology Passive Infrared Ceiling Sensor, 1500 Square Feet Coverage, With Relay

Standard Passive Infrared Technology requires a clear, unobstructed line of sight for detection, because it senses occupancy as movement of heat emitted from the body against the background space. A segmented Fresnel lens divides a coverage area into zones. Movement across zones is interpreted as occupancy. Excellent for small room control.

  • Coverage 1500 sq. ft. (360°) with photocell and isolated relay, low voltage sensor
  • Long range major motion detection
  • Office White ABS enclosure blends with ceiling tile
  • Relay to interface with auxiliary systems such as HVAC
  • Red LED indicates passive infrared detection
  • "Install and Forget" operation. Auto-adjusting adaptive technology eliminates manual adjustments

With Photocell and Relay

Add to List

More Options

Where to Buy

Product Details

General

Application Compatible with most LED and CFL
Color
  • Office White
  • Blanc
Environmental Conditions Indoor Dry Unless Protected By Additional Means
Humidity 0% to 95% non-condensing relative humidity
Indicator(s) Type PIR= Red LED
Item Type Low voltage Ceiling Sensors
Load Capacity Load Is A Function Of The Control Unit
Material ABS (Acrylonitrile butance styrene - Thermoplastic polymer)
Material - Mounting Hardware Screw Mounting
Mounting Type Ceiling Mount
OEM Brand Name Hubbell Wiring Device-Kellems
Operating Cycles 6,000 Cycles Minimum
Operating Temperature 32°F to 104°F (0°C to 40°C) with rate of change not exceeding 20°F(11°C) per hour
Performance
  • Controls - Ambient Light - 1 to 1000 foot candles
  • Controls - Sensitivity - Adaptive 0 to 100%
  • Controls - Time Delay - Test (8 seconds), adaptive 8 to 40 minutes
  • Electrical - Isolated Relay - Normally open and normally closed terminals available
  • Electrical - Power Requirements - 24V DC nominal, 33mA from Hubbell CU series control unit
  • Environmental - Operating Temperature - 32°F to 104°F (0°C to 40°C) with rate of change not exceeding 20°F (11°C) per hour
  • Environmental - Storage Temperature - -20°F to 150°F (-29°C to 65°C), 0% to 95% non-condensing relative humidity
  • Sensing Indicators - Passive Infrared - Red LED
Photocell Yes
Series Passive Infrared
Storage Temperature Range -20°F to 150°F (-29°C to 65°C)
Style Ceiling Mount
Type
  • Sensors
  • Sensors
UPC 783585392523

Dimensions

Diameter 4.5 in
Height 1.5 in
Mounting Height 8-12 ft

Electrical Ratings

Sensitivity Adaptive 0 to 100%
Supply Voltage 24V DC From Control Unit
Voltage Rating 24 VDC
Voltage Rating Description 24V DC

Certifications and Compliance

Industry Standard(s)
  • ASHRAE 90.1 Compliant
  • cULus Listed To UL244A

Logistics

Carton Quantity 10