text.skipToContent text.skipToNavigation

PVI-LP Arrester (15.3 kV MCOV / Uc)

by OHIO BRASS 

Catalog ID: 3028153001

IEEE Intermediate Class Polymer Housed Surge Arrester

Product Details

General

Color Gray Housing
Material ESP™ Polymer Housing
Mounting Hardware Single Eyebolt Terminals
Type Intermediate

Dimensions

Maximum Operating Altitude 12000 ft

Electrical Ratings

Current - Low Current Long Duration (LCLD) Test 550
Frequency Rating 48-62 Hz
MCOV 15.3 kV
Maximum .5 Microsecond Discharge Volts @ Classifying Current 51.6 kV
Maximum Discharge Voltage
  • 40.9 kV @ 1.5 kA
  • 43.2 kV @ 3 kA
  • 45.2 kV @ 5 kA
  • 48.8 kV @ 10 kA
  • 54 kV @ 20 kA
  • 60.9 kV @ 40 kA
Pressure Relief Capability-Symmetrical rms (kA) 40
Time - Low Current Long Duration (LCLD) Test 2000
Withstand Voltage - 60 Hz Wet 40.6
Withstand Voltage - Lightning Impulse 63.4

Certifications and Compliance

Industry Standard(s) IEEE

Resources/Downloads

Videos

Hubbell Power Systems Metal Oxide Varistor (VI01022E0718)