Brand: Electro Composites
Catalog ID: 110-023-T-453-01
Electro Composites SDC™ composite bushings are designed to provide the toughest, cleanest and safest bushing solution for all HV applications. We make standard OEM and aftermarket form-fit-function replacement bushings for substation transformers, GSU transformers, oil circuit breakers, switchgear, wall/floor (air-air and oil-oil), HVDC and other applications. Available from 1kV up to 170kV with current ratings up to 21,500A. SDC™ (Solid Dielectric Capacitor) bushings have a one-piece cycloaliphatic epoxycore and integral sheds. All SDC bushings are solid dielectric insulation – oil–free construction, capacitance graded condenser core with internal CT pocket/ground shield and a flange test tap, available in bottom connected or draw-lead configurations. Made in accordance with the most current bushing standards: IEEE C57.19.01, CSA C88.1, IEC 60137.
For Bushing Test Terminals, please see here
Application
Transformer
Bottom Terminal Type
2-12
Catalog Number
110-023-T-453-01
Color
Gray
Immersion Type - Above Flange
Air
Immersion Type - Below Flange
Oil
Material - Flange
Aluminum
Material - Insulation
APG-02 - Cycloaliphatic Epoxy
Mounting Position
Vertical to Horizontal
Number of Flange Mounting Holes
4
Series
SDCâ„¢ Series
Test Tap
No
Top Terminal Type
2-12
Type
SDC - Solid Dielectric Capacitor
Above Flange Length
10.88 in
Below Flange Length
24 in
Depth
6.63 in
Diameter - Above Flange Maximum
5.75 in
Diameter - Below Flange Maximum D <gt/> 1"
3.69 in
Diameter - Below Flange Maximum P
3.69 in
Diameter - Conductor Outside Under Insulation
2 in
Diameter - Live Part Bottom
2 in
Diameter - Live Part Top
3.5 in
Diameter - Rod / Tube
2 in
Dimensions
34.88 in x 6.63 in x 6.63 in
Effective Length - Bottom Terminal
3 in
Effective Length - Top Terminal
2.5 in
Flange Mounting Hole Bolt Circle
7.25 in
Flange Mounting Hole Diameter
0.63 in
Flange Outside Diameter
6.63x6.63
Height
6.63 in
Length
34.88 in
Length - Ground Shield
16.5 in
Length - Insulated Section
26.98 in
Length - Insulation Above Flange
4.6 in
Length - Insulation Below Flange
3.2 in
Length - Live Part Bottom
4.3 in
Length - Live Part Top
3.6 in
Length - Minimum Oil Immersion Level
16.5 in
Sealing Surface Inside Diameter
4.11 in
Sealing Surface Outside Diameter
6 in
Thickness
0.845 in
Top Terminal Min. Thread Length
2.5 in
Weight
55 lb
Width
6.63 in
BIL
110 kV
Current Rating
2250 A
kV Class
15 kV
Minimum Creepage
12.5 in
Minimum Strike
6.3 in
Withstand Voltage - 60 Hz Dry
50 kV
Industry Standard(s)
IEEE C57.19.01
Immersion Type - Above Flange
Air
Immersion Type - Below Flange
Oil
Bottom Terminal Type
2-12
Mounting Position
Vertical to Horizontal
Number of Flange Mounting Holes
4