HUBBELL
Image of 110-001-T-381-00 SDCâ„¢ Series, Composite Bushing - 50kV

SDCâ„¢ Series, Composite Bushing - 50kV

Brand: Electro Composites

Catalog ID: 110-001-T-381-00

SDCâ„¢ 50kV-50 A Transformer Condenser Bushing, Solid-Dielectric-Capacitor Type, Rated per IEEE C57.19.01, Bottom Connected for Air-to-Oil Applications, 1.5" Min. Oil Immersion Level/Ground Shield Length, 35.4" Min. Creepage Length

Electro Composites SDC™ composite bushings are designed to provide the toughest, cleanest and safest bushing solution for all HV applications. We make standard OEM and aftermarket form-fit-function replacement bushings for substation transformers, GSU transformers, oil circuit breakers, switchgear, wall/floor (air-air and oil-oil), HVDC and other applications. Available from 1kV up to 170kV with current ratings up to 21,500A. SDC™ (Solid Dielectric Capacitor) bushings have a one-piece cycloaliphatic epoxycore and integral sheds. All SDC bushings are solid dielectric insulation – oil–free construction, capacitance graded condenser core with internal CT pocket/ground shield and a flange test tap, available in bottom connected or draw-lead configurations. Made in accordance with the most current bushing standards: IEEE C57.19.01, CSA C88.1, IEC 60137.

  • SDCâ„¢ - Solid Dielectric Capacitance Graded Composite Construction
  • EC-APG-02 Cycloaliphatic Epoxy Compound for Optimal Performance
  • No oil, paper or porcelain
  • Can be mounted vertically or horizontally
  • Meets IEEE C57.19.01 Electrical and Mechanical Requirements

For Bushing Test Terminals, please see here

General

Application

Transformer

Bottom Terminal Type

3/8-16

Catalog Number

110-001-T-381-00

Color

Gray

Immersion Type - Above Flange

Air

Immersion Type - Below Flange

Oil

Material - Flange

Aluminum

Material - Insulation

APG-02 - Cycloaliphatic Epoxy

Mounting Position

Vertical to Horizontal

Number of Flange Mounting Holes

4

Series

SDCâ„¢ Series

Test Tap

No

Top Terminal Type

3/8-16

Type

SDC - Solid Dielectric Capacitor

Dimensions

Above Flange Length

16.25 in

Below Flange Length

5.5 in

Depth

6.25 in

Diameter - Above Flange Maximum

7.47 in

Diameter - Below Flange Maximum D <gt/> 1"

2.98 in

Diameter - Below Flange Maximum P

2.98 in

Diameter - Conductor Outside Under Insulation

1.25 in

Diameter - Live Part Bottom

1.25 in

Diameter - Live Part Top

2.75 in

Diameter - Rod / Tube

1.25 in

Dimensions

21.75 in x 6.25 in x 6.25 in

Effective Length - Bottom Terminal

1.00 in

Effective Length - Top Terminal

1.00 in

Flange Mounting Hole Bolt Circle

5.25 in

Flange Mounting Hole Diameter

0.5 in

Flange Outside Diameter

6.25 in

Height

6.25 in

Length

21.75 in

Length - Ground Shield

1.50 in

Length - Insulated Section

19.2 in

Length - Insulation Above Flange

11.20 in

Length - Insulation Below Flange

2.80 in

Length - Live Part Bottom

1.20 in

Length - Live Part Top

1.50 in

Length - Minimum Oil Immersion Level

LOWER END TO BE FULLY IMMERSED

Sealing Surface Inside Diameter

3.14 in

Sealing Surface Outside Diameter

4.75 in

Thickness

0.865 in

Top Terminal Min. Thread Length

1 in

Weight

27 lb

Width

6.25 in

Electrical Ratings

BIL

110 kV

Current Rating

50 A

kV Class

50 kV

Minimum Creepage

35.4 in

Minimum Strike

14.5 in

Withstand Voltage - 60 Hz Dry

55 kV

Certifications And Compliance

Industry Standard(s)

IEEE C57.19.01

Operational

Immersion Type - Above Flange

Air

Immersion Type - Below Flange

Oil

Configuration

Bottom Terminal Type

3/8-16

Mounting Position

Vertical to Horizontal

Number of Flange Mounting Holes

4