General

Cantilever Bending Strength - Max. 1270 LB
Cantilever Bending Strength - Routine 635 LB
Fitting - Ground End 5'' Bolt Circle, 5/8'' through hole
Fitting - Live Line End 5'' (127mm) Bolt Circle 5/8'' (16mm) Tapped Hole
Number of Sheds 98
Shed Style Uniform

Dimensions

Diameter - Shed(s) 5.06
Length - Effective 128.3 in
Rod Diameter 2.500 in
Thickness - Housing > 3MM

Electrical Ratings

Arc Distance - Dry 119.3 IN (3030 MM)
Creep and Leakage Distance 309 IN (7849 MM)
Critical Impulse Flashover (CIFO) - Negative 1940
Critical Impulse Flashover (CIFO) - Positive 1855
Flashover Voltage - 60 Hz Dry 1150
Flashover Voltage - 60 Hz Wet 920
kV Class 345.00 kV