Image of  CSB/656/N | Ex d & Ex e | Cable Gland

CSB/656/N | Ex d & Ex e | Cable Gland

Brand: Hawke

The Hawke CSB 656N is a Group II certified barrier conduit stopper box, with a female running coupler, suitable for installation in Zone 1/21 and Zone 2/22 hazardous areas. Dual Certified ATEX/IECEx (along with many more) for use in Increased Safety (Exe), Flameproof (Exd), Restricted Breathing (ExnR) and Dust (Ext) protection concepts. For use with conductors, non-armoured elastomer and plastic insulated cables installed in conduit.

  • Metallic body construction
  • Fully Inspectable Removable Compound Chamber
  • Available with QSP (2-part hand mix compound) as standard. Cure time of 30 minutes
  • Female threaded running coupler for cable gland or conduit entry
  • Available with metric or NPT entry and female threadforms

Download the Hawke Technical Guide for more information on installation rules and regulations.
Click here for Resource Search tool.

General

Application

Hazardous Areas Zone 1, Zone 21, Zone 2, Zone 22

Ingress Protection

  • IP66 to IEC/EN 60529
  • Deluge Protection to DTS01

Material

Manufactured in Brass, Nickel Plated Brass or 316L Stainless Steel

Operating Temperature

-60°C to +80 °C

Series

Cable Glands for Group II Hazardous Areas

Certifications And Compliance

ATEX File Number

CML19ATEX1170X, and IECEx CML19.0048X

Certification

  • IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31
  • UL 60079-0, UL 60079-1, UL 60079-7, UL 2225
  • CSA 22.2 No: 60079-0, CSA 22.2 No: 60079-1, CSA 22.2 No: 60079-7, CSA 22.2 No: 60079-31
  • ISA 60079-31

Certified Listed

  • ATEX: CML 19ATEX1170X / CML 19ATEX4507X (Ex nR)
  • CCC: 2020312313000316
  • cCSAus: 1024328
  • DNV: TAE0000BS
  • EQM: 20-11-27224/Q20-11-000979/NB0007
  • IECEx: CML 19.0048X / CML 21.0012X (Ex nR)
  • Inmetro: IEx 14.0272X
  • KCs: 17-KA4BO-0150X to 0158X
  • PESO: P450038
  • SONCAP: LCOGB049552-0500
  • UKEx: CML 21UKEX1164X / CML 21UKEX4133X (Ex nR)
  • EAC: KZ 7100841.01.01.03125

CSA File Number

CSA1015065 for Marine Shipboard Cable

Hazardous Rating(s)

  • Ex II 2GD Ex db eb IIC Gb
  • Ex nR IIC Gc
  • Ex tb IIIC Db
  • Class I Div 1 ABCD
  • Class II Div 2 EFG and Class III
  • Class I, Zone I, AEx db IIC Gb
  • AEx eb IIC Gb
  • Zone 21, AEx tb IIIC Db

Industry Standard(s)

  • IEC/EN 60079-0, 1, 7, 15, 31
  • CSA 60079-0, 1, 7, 31
  • CSA C22.2 No. 0-10, CSA C22.2 No. 174-18
  • UL2225
  • UL1203
  • UL 514B

Ratings

IK10 to IEC 62262

Operational

Operating Temperature

-60°C to +80 °C