Transcript
00:00The following video is for a four piece installation.
00:03When beginning preparation for the installation, you will need to take the YSR connector and
00:08position it over the cable and mark it, strip the installation to the mark and be careful not
00:14to nick the cable during stripping of the wire.
00:16Once you have stripped the wire, insert the cable into the connector,
00:20insert the connector in the dye and ensures that the cable is fully inserted.
00:25The cable strands must be visible through the inspection holes.
00:29Now you can compress between markings beginning near the center of the connector to make the
00:33connection, make sure you always cramp from the center going outwards because of the different
00:39barrel sizes. Some splices require more than one piece of
00:43clear heat shrink tubing to be properly insulated.
00:46Once the connection is made slide, the larger tube over barrel one cable and the smaller
00:51tubes onto the barrel two cable.
01:00Then using the same steps above connect barrel two.
01:10Once the splice is fully crimped slide, the smaller piece of heat shrink over a barrel two
01:15until it stops apply heat until full shrinkage is reached,
01:21move the second piece from barrel two cable over barrel two again until it stops,
01:27apply heat until full shrinkage is reached.
01:32Repeat these steps for the third piece of heat shrink, apply heat until full shrinkage is
01:37reached. You will now need to slide the tube from barrel
01:42one over the completed assembly and apply heat for heating temperature.
01:47Use a lower temperature heat shrink and a low wattage gun or the low settings on a multiple
01:53wattage gun. For these clear tubing installations,
01:56100 and 35 °C 275 °F is the max your installation is now
02:03complete.