Confirms a line is de-energized prior to performing maintenance. A field intensity meter, it is calibrated to read approximate phase-to-phase voltage when connected to any phase conductor. Responds to magnitude of field gradient between its end probe and floating electrode (at the universal hotstickattachment fitting). If the universal fitting is close to a ground, another phase or another voltage source, reading should be high. If it’s close to a jumper or equipment of the same phase, the reading should be low. Gives metered readout capable of distinguishing actual line voltage from static or feedover from an adjacent line. Numerical readings can be compared with numerical rather than subjective judgments associated with “fuzz sticking” or “glow-detecting”.
Catalog Number
T4033228
Indicateur EU RoHs
No
Type
Lighted Analog Dial
Type de matériel
Standard
UPC
096359236863
Mesure du poids
4 kg
Poids
9 lb
Tenue en tension
Up to 40kV
Achetez des produits qualifiés aux États-Unis
TAA Compliant (All status valid till December 2024)
Emballage standard
1