Brand: OHIO BRASS
Catalog ID: MH4300GM240AA
Application
Substation
Catalog Number
MH4300GM240AA
Color
Gray Housing
Material
Porcelain Housing
Mounting Position
Upright
Type
Station
Bolt Circle Diameter
254 mm
Diameter - Single Bolt Hole(s)
14 mm
Height
2429 mm
Minimum Mounting Spacing on Center (Sea Level) - Phase to
55.1 in (1400 mm)
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
63 in (1599 mm)
Creep and Leakage Distance
252.5 in (6414 mm)
Duty Cycle
240 kV
Frequency Rating
48-62 Hz
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
482 kV
Maximum Switching Surge Protective Level @ 2000A
500 kV
Maximum Switching Surge Protective Level @ 500A
469 kV
MCOV
192 kV
Minimum Strike
1880 mm
Pressure Relief Capability-Symmetrical rms (kA)
63
Voltage - Line
300 kV
Withstand Voltage - 60 Hz Wet
588 kV
Withstand Voltage - Lightning Impulse
1018 kV
Withstand Voltage - Switching Impulse
936 kV
Conductor Type
Cu/Al (AWG #4 - 500 MCM)
Industry Standard(s)
IEC
Mounting Position
Upright