Brand: RFL Electronics
Catalog ID: RFL_GARD_8000_RCS
Catalog Number
RFL_GARD_8000_RCS
Humidity
Up to 95 percent at +40° C (+104° F), non-condensing
Input Power - Max
100 W
Interface Type
T1/E1;RS-449, 56 -768 kbps;X.21, 64-768 kbps;V.35, 64-768 kbps;G.703, co-directional, 64 kbps;ANSI C37.94 fiber;Fiber, multi-mode or singlemode, up to 100 km;RS232 Async (pass-thru only);Audio Tone, 2 wire or 4 wire;Power Line Carrier, ON/OFF or FSK selectable
Mounting Method
19” Rack Mount
Radio Frequency Interference
RFI Susceptibility: ANSI PC37.90.2 (35 Volts/Meter), IEC 255-22-3 (RFI Class III)
Temperature Rating
Operating: -20° C to +75° C (-4° F to + 165° F), Storage: -40° C to +85° C (-40° F to +185° F)
Cubic Capacity
NaN cu.in
Depth
14.5 in
Height
Width
19 in
Dielectric Strength
All contact inputs, solid-state outputs, power supply inputs and relay outputs meet the following specifications: ANSI C37.90-1989 (Dielectric), ANSI C37.90.1-2002 (SWC and Fast Transient), IEC 255-5 (1500 Vrms Breakdown Voltage and Impulse Withstand), IEC 255-22-1 (SWC Class III), IEC 255-22-2 (ESD Class III), IEC 255-22-4 (Fast-Transient Class III), IEC 834-1.
Input Voltage
Voltage Rating