Brand: OHIO BRASS
Catalog ID: SVN420GA335AA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN420GA335AA
Color
Gray Housing
EU RoHS Indicator
Contact Manufacturer
Material
Silicone Polymer Housing
Mounting Hardware
Single Eyebolt Terminals
Mounting Position
Upright
Type
Station
UPC
096359402589
Bolt Circle Diameter
10 in
Depth
60 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Ring
80 in / 46 in
Diameter - Single Bolt Hole(s)
0.56 in
Height
158 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
1951 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
2220 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
60 in
Creep and Leakage Distance
486.6 in (12360 mm)
Duty Cycle
420 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
1109 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
823.0 kV
Maximum Switching Surge Protective Level @ 2000A
852.0 kV
Maximum Switching Surge Protective Level @ 500A
799 kV
MCOV
335 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
1008 kVrms
Withstand Voltage - Lightning Impulse
1939 kV
Withstand Voltage - Switching Impulse
1677 kV
Conductor Type
Aluminum/Copper
EU RoHS Indicator
Contact Manufacturer
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position
Upright